Combined TOG result

Cormar Kingston Elite and Duralay Heatflow for Carpet: combined TOG for underfloor heating

The combined TOG for Cormar Kingston Elite over Duralay Heatflow for Carpet, worked against the UHMA underfloor heating rule.

1.52.5
0.95TOG in situ
Pass · limit 2.5
Published TOG stack (carpet + underlay)
carpet 1.2
underlay 0.75
limit

Combined against the UHMA 2.5 TOG underfloor-heating limit. Under 1.5 also suits a low-temperature heat pump.

Carpet TOGUnderlay TOGPassMarginalFail
Combined in-situ TOG is 0.95, under the 2.5 TOG limit, so Cormar Kingston Elite with Duralay Heatflow for Carpet is suitable for a standard underfloor heating system. It is also under 1.5 TOG, so it suits a low-temperature heat pump run.
The combined-TOG calculation
CarpetCormar Kingston Elite (1.2 TOG)
UnderlayDuralay Heatflow for Carpet (0.75 TOG)
Published sum1.95 TOG
UHMA in-situ correctionminus 1 TOG
Combined in-situ TOG0.95 TOG
Standard UFH limit2.5 TOG
Heat pump targetunder 1.5 TOG

Cormar Kingston Elite is rated 1.2 TOG and Duralay Heatflow for Carpet is rated 0.75 TOG. Laid together the combination is what the underfloor heating has to warm through.

The published TOG figures add to 1.95. The UHMA rule subtracts 1 TOG because tests showed real in-situ resistance runs about a TOG below the paper sum, giving 0.95 TOG. That clears both the standard limit and the tighter heat-pump target.