TogCheck
Combined TOG result

Cormar Trilogy Bronte and Duralay Technics 5: combined TOG for underfloor heating

The combined TOG for Cormar Trilogy Bronte over Duralay Technics 5, worked against the UHMA underfloor heating rule.

1.52.5
0.96TOG in situ
Pass · limit 2.5
Published TOG stack (carpet + underlay)
carpet 1.4
underlay 0.56
limit

Combined against the UHMA 2.5 TOG underfloor-heating limit. Under 1.5 also suits a low-temperature heat pump.

Carpet TOGUnderlay TOGPassMarginalFail
Combined in-situ TOG is 0.96, under the 2.5 TOG limit, so Cormar Trilogy Bronte with Duralay Technics 5 is suitable for a standard underfloor heating system. It is also under 1.5 TOG, so it suits a low-temperature heat pump run.
The combined-TOG calculation
CarpetCormar Trilogy Bronte (1.4 TOG)
UnderlayDuralay Technics 5 (0.56 TOG)
Published sum1.96 TOG
UHMA in-situ correctionminus 1 TOG
Combined in-situ TOG0.96 TOG
Standard UFH limit2.5 TOG
Heat pump targetunder 1.5 TOG

Cormar Trilogy Bronte is rated 1.4 TOG and Duralay Technics 5 is rated 0.56 TOG. Laid together the combination is what the underfloor heating has to warm through.

The published TOG figures add to 1.96. The UHMA rule subtracts 1 TOG because tests showed real in-situ resistance runs about a TOG below the paper sum, giving 0.96 TOG. That clears both the standard limit and the tighter heat-pump target.

Related checks

Sources: UHMA guidance on underfloor heating with carpet and underlay (combined-TOG rule) · How to calculate a combined TOG (UHMA formula, worked) · Cormar Carpets published carpet TOG values · Interfloor / Duralay Technics 5 underlay datasheet